banner products tws ducati energia - logo trans

Three-phase reactors p = 12.5%

Technical Specifications

– Mains voltage 400V 50Hz
– Power supply: three-phase + PE
– Continuous current harmonic distortion allowed:

  • 20% In at 150 Hz
  • 35% In at 250 Hz
  • 15% In at 350 Hz

– Tuning frequency: 141 Hz
– Insulation: 660 V
– Linearity up to 1.8 Ip/In
– Figure of merit: Q > 20
– Induction value at In: < 0.8Tesla
– Class H materials
– Thermal protection via thermistor with NC contact.

Size (mm)
Part n.
315.99.
Power output
(kVAr)
Inductance
(mH)
I RMS
(A)
A B C D E F G H Weight
(Kg)
C
theorical
(µF)
Proposed
capacitors
416.47.xxxx
1005 10 3 x 7,28 16,7 200 240 130 88 118 165 9 20 13 3 x 58 4200
1010 12,5 3 x 5,82 20,9 200 240 140 98 128 165 7 20 15 3 x 73 4260
1012 15 3 x 4,85 25,1 200 240 140 98 128 205 7 20 20 3 x 87 4100+4150
1015 20 3 x 3,64 33,4 200 240 140 98 128 205 7 20 21 3 x 116 4360
1020 25 3 x 2,91 41,8 200 240 150 113 143 220 9 20 25 3 x 145 4150+4310
1025 40 3 x 1,82 66,8 250 300 165 120 160 285 9 25 39 3 x 232 2×4360
1030 50 3 x 1,46  83,6 250 300 175 130 170 285 9 25 45 3 x 290 2x(4150+4310)