banner products tws ducati energia - logo trans

Three-phase reactors p = 7%

Technical Specifications

– Mains voltage 400V 50Hz
– Power supply: three-phase + PE
– Continuous current harmonic distortion allowed:

  • 2% In at 150 Hz
  • 35% In at 250 Hz
  • 15% In at 350 Hz

– Tuning frequency: 189 Hz
– Insulation: 660 V
– Linearity up to 1.8 Ip/In
– Figure of merit: Q > 20
– Induction value at In: < 0.8Tesla
– Class H materials
– Thermal protection via thermistor with NC contact.

Size (mm)
Part n.
315.99.
Power output
(kVAr)
Inductance
(mH)
I RMS
(A)
A B C D E F G H Weight
(Kg)
C
theorical
(µF)
Proposed
capacitors
416.47.xxxx
1005 10 3 x 3,84 16,3 150 180 110 82 110 180 M* 20 9.5 3 x 62 3150
1010 12,5 3 x 3,07 20,4 150 180 120 92 120 180 M* 20 11 3 x 77 4260
1012 15 3 x 2.55 26.8 200 240 130 85 118 166 9 20 13 3 x 94 2×4150
1015 20 3 x 1,91 32,7 200 240 130 88 118 165 9 20 13 3 x 123 4150+4260
1020 25 3 x 1,53 40,8 200 240 140 98 128 165 9 20 15 3 x 154 2×4260
1025 40 3 x 0,96 65,2 200 240 140 98 128 205 9 20 21 3 x 247 4200+(2×4310)
1030 50 3 x 0,77  81,6 200 240 150 113 143 220 9 20 25 3 x 308 4×4260