banner products tws efen - logo trans

Technical data

HRC battery fuse-links DC 550 V for UPS

Order No. Pack Size / Type
35177.0010 3 00 E
35177.0030 3 00 G
35177.0040 3 00 H
35177.0050 3 00 A
35177.0060 3 00 B
35177.0070 3 00 C
35177.0080 3 00 D
35178.0010 3 1 A*
35178.0020 3 1 B*
35178.0030 3 1 C*
35179.0010 3 2 A
35179.0020 3 2 B
35180.0010 1 3 A
35180.0020 1 3 B
35180.0030 1 3 C
35183.0020 1 4 C
35183.0030 1 4 D
35183.0040 1 4 E
* Size 2 (Compact version 2/1)

 

Dimension HRC battery fuse-links DC 550 V for UPS
Size a1 a2 b c e1 e2 f g
00 78,5 53 15 35 40 28 12,5 47
1 150 71 25 48 45 45 10 65
2 150 72 30 48 59 59 14,5 65
3 150 72 40 60 70 70 15 65
4a 200 98 50 85 110 102 28 87

 

Technical data for single-pole NH fuse-switches acc. to VDE 0660 T107/IEC/EN 60 947/3

For LV fuse-links acc. to DIN 43620/1 1) Size 00 1 2 3 4a
Rated operational current Ie A 160 250 400 630 1250
16002)
Conventional free air thermal current Ith A 160 250 400 630 1250
16002)
Rated operational voltage Ue V 690 690 690 690 690
Rated insulation voltage Ui V 800 800 800 800 800
Rated impuls withstand voltage Uimp kV 8 8 8 8 8
Rated conditional short circuit current kA 50 50 50 50 50
(when protected by fuse-links)
Weight without fuse-links
Version Sc kg 0,38 2,4 2,4 2,5 4,2
Version Sb Sc 0,36 2,0 2,0 2,4 4,2
Utilization category IEC/EN 60 947/3 Ue = 400 V AC-22 B AC-22 B AC-22 B AC-22 B AC-22 B
Ue = 690 V AC-21 B AC-21 B AC-21 B AC-21 B AC-21 B
Ue = 440 V3) DC-21 B DC-21 B DC-21 B DC-21 B DC-21 B
Permissible ambient air temperature °C – 40 bis/up to + 55
Notice:

1) When using gR-fuse-links (EN 60269-4), please ask for information.
2) 1600A possible with NH fuse-links up to a rated power dissipation of 140 W.
3) Size 00 le = 100 A.

 

AC 690 V/DC 550 V, single-pole, size 00-4a

          Torque Torque
Type Size A Order No. Pack Description mech. electr.
For baseplate mounting
Flat terminal M8 00 160 33107.0010 2 NH-Latr. 00 1P SC G4G4 5 Nm 14 Nm
Multiple use terminal U3 (with pressure plate) 00 125 33108.0010 2 NH-Latr. 00 1P SC U3U3 5 Nm 14 Nm
Multiple use terminal U4 00 160 33109.0010 2 NH-Latr. 00 1P SC U4U4 5 Nm 14 Nm
(Pressure plate with contact prism)
Flat terminal M10 1 250 33095.0010 2 NH-Latr. 1 1P SC L5L5 32 Nm 32 Nm
Flat terminal M10 2 400 33096.0010 2 NH-Latr. 2 1P SC L5L5 32 Nm 32 Nm
Flat terminal M12 3 630 33097.0010 2 NH-Latr. 3 1P SC L6L6 32 Nm 40 Nm
Flat terminal M16 4a 1250 33047.0010 1 NH-Latr./Unt. 4a 1P L8L8 40 Nm 56 Nm
1600*

 

        Torque Torque
Branch cable Type Size A Order No. Pack Description mech. electr.
top/bottom choice when mounting For busbar contacting
Flat terminal M8 00 160 33111.0010 2 NH-Latr. 00 1P SB SC G4 14 Nm 14 Nm
Multiple use terminal U3 (with pressure plate) 00 125 33112.0010 2 NH-Latr. 00 1P SB SC U3 14 Nm 4 Nm
Multiple use terminal U4 00 160 33113.0010 2 NH-Latr. 00 1P SB SC U4 14 Nm 4 Nm
(Pressure plate with contact prism)
top Flat terminal M10 1 250 33098.0020 2 NH-Latr. 1 1PO SB SC L5 40 Nm 32 Nm
Flat terminal M10 2 400 33099.0020 2 NH-Latr. 2 1PO SB SC L5 40 Nm 32 Nm
Flat terminal M12 3 630 33100.0020 2 NH-Latr. 3 1PO SB SC L6 40 Nm 40 Nm
Flat terminal M16 4a 1250 33048.0020 1 NH-Latr./Unt. 4a 1PO SB L8 56 Nm 56 Nm
bottom Flat terminal M10 1 250 33098.0010 2 NH-Latr. 1 1PU SB SC L5 40 Nm 32 Nm
Flat terminal M10 2 400 33099.0010 2 NH-Latr. 2 1PU SB SC L5 40 Nm 32 Nm
Flat terminal M12 3 630 33100.0010 2 NH-Latr. 3 1PU SB SC L6 40 Nm 40 Nm
Flat terminal M16 4a 1250 33048.0010 1 NH-Latr./Unt. 4a 1PU SB L8 56 Nm 56 Nm
1600*
* 1600 A: on demand
Click here to see Accessories page