Rated current In A 160 160 250 400 630
Rated voltage Un V 690 690 690 690 690
Current type and rated frequency AC 50Hz AC 50Hz AC 50Hz AC 50Hz AC 50Hz
Rated insulation voltage Ui V 690 690 690 690 690
r.m.s value of the power-frequency test voltage for 60s V 2500 2500 2500 2500 2500
Maximum cut-off current / kA 25 25 38 48 70
(when protected by NH Fuse-Links)
Permissible ambient temperature °C –25 bis +55 / –25 up to +55
Degree of protection DIN/EN 60529/VDE 0470 T1 IP IP3x IP 00 IP 00 IP 00 IP 00
Maximum power dissipation of the NH Fuse-Links W 12 12 32 45 60
Weight without NH Fuse-Links 1-pole kg 0,14 0,34 0,41 0,62
Weight without NH Fuse-Links 3-pole kg 0,33 0,52 1,03 1,22

 