banner products tws hager-logo trans

MCB 80-125A

 HLF199S HMC299
HLE, HLF; “B”-”C” 10000 – 10kA HMB, HMC, HMD; “B”, ”C”, “D” 15000 – 15kA
 HMK399 HMX440
HMK; “C” – 30k HMX; “C” – 50kA

 

Thermal magnetic circuit breakers

curves “B” – “C” – “D”

In 80 to 125 A

These circuit breakers are intended for the protection of the mcircuits against overloads and short circuits in professional premises (from residential to commercial and industrial premises).

  • The circuit breakers curve “B” are particularly recommended for the circuits with long cable length and for residential loads with low in-rush current.
  • The circuit breakers curve “C” are adapted to the protection of the circuits in professional premises.
  • The circuit breakers curve “D” are particularly adapted to the protection of the circuits where the installations are subject to high in-rush currents.

– HMB curve “B” 15000
15 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

– HMC curve “C” 15000
15 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

– HMD curve “D” 15000
15 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

– HMK curve “C”
30 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

– HMX curve “C”
50 kA of 16 – 63 A : width 1.5 ❚ / pole

– HLE curve “B” 10000
10 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

– HLF curve “C” 10000
10 kA of 80 – 100 – 125 A : width 1.5 ❚ / pole

  • These circuit breakers are equipped with reinforced screw cages.
  • A label holder is integrated under the handle to ensure the location of the product.
  • The “OFF” position is clearly shown by a green indicator below the handle.
  • Suitable for isolation (according to IEC 60947-2) : the isolation of the circuit breakers is indicated by a green indicator on the handle.
  • These circuit breakers have quick closing : fast and simultaneous closing of the contacts, independent of the handling speed.
  • That increases the life of the circuit breaker whatever the type of load.

Nominal voltage : 230/400 V

Insulation voltage: 500 V

Options :
– Auxiliary :

  • to visualise the state ON or OFF of the circuit breaker, • to ON/OFF remotely the circuit breaker

– Locking mechanism

– Terminal covers and phase separators

– RCD add-on blocks

– Disassembly capability :

  • Bistable DIN-rail latches (2 positions) upstream and dowstream facilitate the assembly or the disassembling of the circuit breakers on the DIN-rail.

– Terminals with tightening compensation.

  • These circuit breakers are equipped with screw cages with tightening compensation, reinforcement cage, cable holding jaws.
  • These elements contribute to an effective cable tightening over time.

– These circuit breakers are equipped with cable terminals of type “fast on” upstream and downstream to feed an auxiliary low voltage circuit (indicating lights, auxiliary control…)

  • Max. circuit 6A 6 mm2 maxi.

– Lockable handle MCB can be locked in “Off” position by the integrated locking facility on the handle.

  • This lock allows to insert a 2.5-3.5mm plastic cable tie where you can fit a warning card if necessary and allows a safer working environment for all personnel.

– RCD Add-on blocks, simple, quick, adjustable and fixed:

  1. assembly
  2. connection
  3. locking

The assembly of the add-on block is carried out very quickly and easily. Simple and fast : it is a Hager innovation. add-on blocks 125A are available in fixed version and adjustable version.

 Model  Icc/Curve Accessories Fast-on connection Tightening comp. system Lockable handle Front product labelling
 HLE / HLF  10kA / B, C YES NO NO NO YES
 HMB / HMC  15kA / B, C, D YES YES YES YES YES
 HMD
 HMK  30kA /C YES YES YES YES YES
 HMX  50kA /C YES YES YES YES YES