RESYS P40

Type A earth leakage relays

for motor load break

RESYS P40
RESYS P40
Function
  • RESYS P40 earth leakage relays associated with a remote trip breaking device (automatic power breaking), provide the following functions:
    – protection against indirect contact,
    – limitation of leakage currents.
  • They also preventively monitor electrical installations via their (configurable) pre-alarm function or when used as signalling relays.
Advantages
Fully configurable
  • 2 relays with configurable function (alarm or pre-alarm at 50% IΔn).
  • Adjustment of IΔn from 0.03 to 30 A.
  • Time delay 0 to 10 s.
  • Positive or negative security configurable by the user.
  • Selection of toroid ratio.
Tripping accuracy by TRMS measurement
  • Improves immunity to nuisance tripping.
Instantaneous display of permanent leakage currents
  • The LED bargraph provides a real-time display of fluctuations in leakage currents.
Compact 48x48mm panel-mounted unit
  • The adjustment buttons are protected by a sealable cover, while the display of available alarms is displayed directly on the front face of the device.
Improved immunity to EMC interferences
  • The device has new electronics which improve electromagnetic compatibility.
Applications
application RESYS P40
Rapid recognition of an insulation fault increases the availability of the distribution network by preventing accidental power cuts and the resulting loss of production. RESYS P40 are particularly suitable for insertion in electricity control panels with withdrawable compartments.
Protection against fire or explosion risks
  • The use of Residual Differential Devices (with adjustment IΔn ≤ 300 mA) provides protection against the risk of fire or explosion generated by tracking currents to earth, in areas classed as BE2 or BE3 respectively. This protection is mandatory in TT, TN and IT neutral systems.

 

Front panel

front panel RESYS P40 1. Adjustment IΔn.
2. Time delay setting.
3. Configuration micro-switches (x4).
4. “ON” LED.
5. “RESET” pushbutton.
6. “TRIP” alarm LED.
7. LED bargraph (% x IΔn).
8. “TEST” pushbutton.

 

 Characteristics

RESYS P40
Auxiliary power supply US
Frequency 47 … 63 Hz
AC operating zone 0.8 … 1.15 US
DC operating zone 0.8 … 1.05 US
Max. consumption 6 VA (AC) / 5 W (DC)
Insulation (according to IEC 60664-1 standard)
Rated insulation voltage 250 VAC
Rated impulse voltage 2.5 kV (115 VAC) / 4 kV (230/400 VAC)
Degree of pollution Class 3
Threshold values
IΔn setting 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 – 5 – 10 – 30 A
Accuracy of tripping – 20 … – 10% IΔn
Domain of network frequency 15 … 400 Hz
Time delay setting 0 – 0.06 – 0.15 – 0.30 – 0.50 – 0.80 – 1 – 4 – 10 s
PRE-ALARM relay tripping 50% IΔn
Hysteresis of the PRE-ALARM relay 20% IΔn
Alarm
Alarm configuration mode storage / automatic reset
Alarm factory setting storage
Reset manual by pushbutton / using terminal
Output contacts
Number of contacts 2
Type of ALARM 1 contact 250 VAC – 8 A – 2000 VA
Type of ALARM 2 or PRE-ALARM contact 250 VAC – 6 A – 1500 VA
ALARM 1 operating mode negative security(1)
ALARM 2 or PRE-ALARM operating mode positive security(1)
Factory setting of ALARM 1 operating mode negative security
Factory setting of ALARM 2 operating mode positive security
Operating conditions
Operating temperature – 20 … + 55 °C
Storage temperature – 30 … + 70 °C
(1) Negative security: relay activated in case of alarm / Positive security: relay not activated in case of alarm.

 

Case

RESYS P40
Type panel mounting
Dimensions W x H x D 48 x 48 x 107
Case protection index IP 40
Terminal protection index IP 20
Rigid cable cross-section 0.2 … 4 mm2
Flexible cable cross-section 0.2 … 2.5 mm2
Weight 190 g
Cutout 45 x 45 mm

 

Terminals and connections

1 – 2 – 3 : external pushbuttons
4 – 5 : SOCOMEC differential toroid connections
6 – 7 : auxiliary power supplies US
8 – 9 – 10 : alarm relay 1 output
11 – 12 : alarm relay 2 outputs
Note:

  • The earth conductor must not pass through the C.T.
  • For single phase applications, only the live and neutral need to be passed through the C.T.

Cabling:

  • for distances > 1 m, use twisted pair cable between the unit and C.T.
  • Do not connect the shield to earth.

 

References

RESYS P40
Auxiliary power supply US (1) Reference
115 VAC 4942 3711(2)
230 VAC 4942 3723(2)
12 … 125 VDC 4942 3602(2)
(1) Other rating: Please consult us. (2) References and characteristics of closed, split core and rectangular toroids: see “Core balance transformers type A” p.
Description of accessories Reference
Soft protection cover IP65 4942 0000