ATSE* – Automatic equipment

ATS no-break Bypass solution

from 40 to 3200 A

ATSE - Automatic equipment from 40 to 3200 A 1 ATSE - Automatic equipment from 40 to 3200 A 2
Function
  • Automatic transfer of two supply sources to ensure continuity of supply to critical loads such as sprinklers, elevators, water pumps…
  • Guaranteed continuity of the power supply during maintenance and test operations.
  • Complete isolation of the Automatic Transfer Switch ensuring maintenance safety.
  • The association of an ATyS along with a remote interface ATyS D20, will enable an easy configuration, exploitation and visualisation of the data shown on the front of the equipment (timers settings, hysterisis, start/stop of the genset…).
Advantages
No-break load transfer in Bypass mode
Solution certified by a manufacturer
Optional accessories available.
Easy integration
General characteristics
  • From 40 to 3200 A – 4 poles.
  • 230/400 VAC +/- 20%, 50/60 Hz, self-supplied from incoming sources.
  • Normal/Emergency logic control sequence.
  • Voltage and frequency checking of networks I and II.
  • Control of phase rotation.
  • 1 configurable output relay for generator start/stop command.
  • Position I, 0, II control by external dry contact.
  • Manual emergency operation.
  • Auxiliary contacts.
  • MODBUS communication (factory fitted).
  • AUTO / MANU selector.
  • Equipment protection degree: IP41 as standard – Other IP upon request.
  • Hinged door.
  • Wall mounting brackets supplied up to 160 A.
  • Floor standing feet from 250A to 3200 A.
  • Plug-in ATS from 160 A.
  • Phase identification.
  • Mimic panel (3 LEDs; source availability (1 and 2) and load; 16 LED mimic panel optional).
  • Integral protection against direct contact on each functional unit.
  • Steel enclosure
  • Colour: RAL 7035.

 

2 versions
Single Line ATS Bypass
  • It consists of 2 functions: an automatic changeover switch and a single Bypass line connected to the preferred supply source.
ATS Bypass - SINGLE LINE
Double Line ATS Bypass
  • It consists of 3 functions: an automatic changeover switch, an ATS Bypass and a facility for selecting between supply sources when in Bypass.
ATS Bypass - DOUBLE LINE
Use
Normal Position:

  • The load is supplied by the supply source defined as the preferred source. In case of primary source failure, the ATS automatically transfers the load to the alternate source when available.

Bypass position:

  • ATS seamless transfer to the Bypass mode is achieved using the bypss line via Q1 to ensure continuity in the power supply to the load. Changeover switch Q2 is then open to provide complete isolation from the power supply sources and to ensure safe interventions.

Test Position:

  • From the Bypass position, changeover switch Q2 can be closed to supply the ATS and achieve operational checks, without jeopardizing the supply to the load. Transfer to the normal position can then be achieved.

 

References

Standard product – 230 VAC for ATyS M 6e

Single Line Double Line
Rating (A) No. of poles Reference(1) Reference(1)
40 4 P 1785 4004 1786 4004
63 4 P 1785 4006 1786 4006
80 4 P 1785 4008 1786 4008
100 4 P 1785 4010 1786 4010
125 4 P 1785 4012 1786 4012
(1) Network 127/230 VAC, on request.

 

Standard product- 230 VAC for ATyS 6e

Single Line Double Line
Rating (A) No. of poles Reference(1) Reference(1)
160 4 P 1785 4016 1786 4016
250 4 P 1785 4025 1786 4025
400 4 P 1785 4040 1786 4040
630 4 P 1785 4063 1786 4063
800 4 P 1785 4080 1786 4080
1000 4 P 1785 4100 1786 4100
1250 4 P 1785 4120 1786 4120
1600 4 P 1785 4160 1786 4160
2000 4 P 1785 4200 1786 4200
2500 4 P 1785 4250 1786 4250
3200 4 P 1785 4320 1786 4320
(1) Network 277 VAC, on request.

 

Accessories

Customer fit

Description Reference
2 inputs / 2 outputs module (ATyS 6e only) 1599 2001

Extension cabinet

Extension cabinet
Use
  • From 1250A to 3200 A, the standard enclosed ATS Bypass is supplied with connections to allow for Bottom/Bottom or Bottom/Top cable entry.
  • In order to facilitate the wiring, we propose the use of an extension cabinet, which can be mounted to the side of the standard ATS Bypass enclosure, when utilising all other types of connections (TT/TB/BT). The extension cabinet also enables any necessary future adaptation.
Padlockable handle in position 0 Reference
1250 … 2000 1599 9004
2500 … 3200 1599 9005

 

Protection against overvoltages

Protection against overvoltages
Use
  • In order to ensure protection against overvoltages of the equipment, type 1 and 2 surge protection is available.
Rating (A) Reference
40 … 125 1599 9016
250 … 400 1599 9017
630 … 3200 1599 9018

 

Multifunction meter

Multifunction meter
Use
  • Multifunction meters are now available for the display and monitoring of all the electrical parameters.

 

Engine Exerciser

Engine Exerciser
Use
  • The enclosed ATS Bypass can be supplied with a genset exerciser. (configure generator Start/Stop times, enable/disable routines, etc….).
Description Reference
Engine Exerciser 1599 9006

 

Tinned Busbars

Use
  • Tinned busbar option for severe environmental conditions.
Description Reference
250 1599 9007
400 1599 9008
630 1599 9009
800 1599 9010
1000 1599 9011
1250 … 1600 1599 9013
2000 1599 9014
2500 … 3200 1599 9015

Remote ATS Bypass management using Ethernet

Remote ATS Bypass management using Ethernet
Use
  • A serial RS485 connection with MODBUS protocol is factory fitted.
  • An optional module can be integrated to enable communication through Ethernet for the following functions:
    – Alarm management (SNMP protocol),
    – Remote control,
    – Data logging,
    – Consultation through embedded website.
Description Reference
Remote control module 4899 0400

 

Signalling

Signalling
Use
  • To get a global overview of the system status, an optional 16 LED mimic panel is available (voltage availability per phase and device positions).
Mimic panel
Single Line Double Line
Description Reference Reference
40 … 3200 1599 9033 1599 9034

 

Dimensions

from 40 to 160 A ≥ 250 A
Dimensions from 40 to 160 A  Dimensions 250A

 

Wall mounting – Bottom

 Rating (A) Recommended connection
cross-section (mm2)
H
(mm)
L
(mm)
D
(mm)
M
(mm)
N
(mm)
Weight (kg)
40 10 800 800 300 848 752 80
63 16 800 800 300 848 752 80
80 25 800 800 300 848 752 80
100 35 1000 800 300 848 752 80
125 50 1000 800 300 848 752 80
160 70 1000 800 400 848 752 160

 

Floor fixing – Bottom

Rating (A) Recommended connection
cross-section (mm2)
H
(mm)
L
(mm)
D
(mm)
Weight (kg)
250 70 1200 (1) 1000 550 180
400 240 1200 (1) 1000 550 200
630 2×185 1600 (1) 1200 600 600
800 … 3200 (2)
(1) Add 100 mm mm for feet.
(2) Please consult us.

 

Connection (input / output)

  • From 40 to 125A (B/B or T/B or T/T or B/T),
  • From 160 to 400A (B/B or B/T),
  • 630 A (B/B),
  • ≥ 800 A(Please consult us).