DIRIS A60

Multifunction meters – PMD

Energy monitoring and event analysis – dimensions 96×96 mm

DIRIS A60
Function
  • DIRIS A60 is a panel mounted multifunction meter which incorporates all functions of the DIRIS A40 with the addition of enhanced data logging functions, recording curves for quality events.
Advantages
Easy to use
  • Thanks to its large backlit LCD display and its multiple viewing screens with direct key access, the DIRIS A60 provide clear readings and are easy to use. It directly display a number of multi-measurement and metering values : ± kWh, ± kvarh, kVAh, I, U, V, F, P, Q, S, PF, etc.
Detects wiring errors
  • An integrated test function can be utilised to detect incorrect wiring and to automatically correct CT installation errors.
Compliant with IEC 61557-12
  • IEC 61557-12 is a high-level standard for all PMDs (Performance Monitoring Devices) that are designed to measure and monitor electrical parameters in distribution networks.
  • Compliance with IEC 61557-12 ensures a high level of equipment performance, in terms of metrology, and the mechanical and environmental aspects (EMC, temperature, etc.).
Management softwares
  • Optional Ethernet module with Webserver function: For measurement monitoring, data exploitation and the export of load curves remotely without a specific software (web browser access).
  • Analysis software: For the analysis of events data in  order to improve the reliability of the electrical installation.
  • Easy Confic software: For quick and easy remote device configuration; configuration files can be copied from and sent to the DIRIS A60, or they can be created without communication and sent at a later time. Multiple devices can be configured from a single file, which is especially useful for OEMs and panel builders.
Conformity to standard EN 50160
  • EN 50160 is a standard which defines events relating to the quality of electrical networks. The DIRIS A60 captures voltage events in accordance with this standard.
Principle diagram
Functions
Multi-measurement Other functions: Multi-measurement
In addition to the functions of the DIRIS A40,
Currents
the DIRIS A60 also:
– instantaneous: I1, I2, I3, In, Isystem
– average/maximum average: I1, I2, I3, In
  • Show the current and voltage unbalance
  • Show the tangent φ
  • Stores the load curves (60 days with an interval of 10 minutes) for the active, reactive and apparent power: ΣP±; ΣQ±; ΣS
  • Detects and stores the last 40 events concerning: overvoltage, voltage dips, cut-offs, overcurrent
– unbalance: U unb
Voltages & frequency
– instantaneous: V1, V2, V3, U12, U23, U31, F, Vsystem, Usystem
– average/maximum average: V1, V2, V3, U12, U23, U31, F
– unbalance: U unb
For each stored event, the DIRIS A60 records the Power
relevant RMS 10 ms interval curves for the voltages – instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS
V1, V2, V3, U12, U23, U31 and the currents I1, I2, – maximum average: ΣP, ΣQ, ΣS
I3, In, giving a total of 400 curves. – predictive: (ΣP), (ΣQ), (ΣS)
Power factor
– instantaneous: 3PF, ΣPF
– instantaneous total tangent φ
– instantaneous, average and max. average unbalance
Temperatures(1)
– internal
– external via 3 PT100 sensors
Metering Harmonic analysis (level 63)
 – Active energy: + kWh Total harmonic distortion
– Reactive energy: + kVarh – Currents: thd I1, thd I2, thd I3, thd In
– Apparent power: kVAh – Phase-to-neutral voltage: thd V1, thd V2, thd V3
– Hours – Phase-to-phase voltage: thd U12, thd U23, thd U31
Individual
– Currents: HI1, HI2, HI3, HIn
– Phase-to-neutral voltage: HV1, HV2, HV3
– Phase-to-phase voltage: HU12, HU23, HU31
Events (1) Load curves(1)
– Alarms on all electrical values – Active and reactive power: ΣP± ; ΣQ±
– Voltages & frequency: V1, V2, V3, U12, U23, U31, F
Communications(1) Inputs / Outputs (1)
– 0/4 – 20 mA – Pulse metering
– RS485 MODBUS RTU – Remote control/command
– Ethernet – Alarm report
  (MODBUS TCP or RTU over TCP and Web server) – Pulse report
– Ethernet
  (MODBUS TCP or RTU over TCP and Web server)
  with RS485 MODBUS RTU gateway
(1) Available on specific version (see the following pages).

 

Front panel

1. Backlit LCD display.
2. Direct access key for currents and test function.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive, and apparent powers and power factor.
5. Direct access key for maximum and average current and power values.
6. Direct access key for harmonic values.
7. Direct access key for energies, hour meter and programming menu.

 

Electrical characteristics

DIRIS A60
Current measurement on insulated inputs (TRMS)
Via CT primary 9 999 A
Via CT secondary 1 or 5 A
Measurement range 0 … 11 kA
Input consumption ≤ 0.1 VA
Measurement updating period 1 s
Accuracy 0.2 %
Permanent overload 6 A
Intermittent overload 10 In for 1 s
Voltage measurements (TRMS)
Direct measurement between phases 50 … 700 VAC
Direct measurement between phase and neutral 28 … 404 VAC
VT primary 500 000 VAC
VT secondary 60, 100, 110, 173, 190 VAC
Input consumption ≤  0.1 VA
Measurement updating period 1 s
Accuracy 0.2 %
Permanent overload 800 VAC
Current-voltage product
Limitation for 1A CT 10 000 000
Limitation for 5A CT 10 000 000
Power measurement
Measurement updating period 1 s
Accuracy 0.5 %
Power factor measurement
Measurement updating period 1 s
Accuracy 0.5 %
Frequency measurement
Measurement range 45 … 65 Hz
Measurement updating period 1 s
Accuracy  0.1 %
Energy accuracy
Active (according to IEC 62053-22) Class 0.5 S
Reactive (according to IEC 62053-23) Class 2
Auxiliary power supply
Alternating voltage 110 … 400 VAC
AC tolerance ± 10 %
Direct voltage 120 … 350 VDC
DC tolerance ± 20 %
Frequency 50 / 60 Hz
Consumption ≤ 10 VA
2 inputs / 2 outputs module: Outputs (alarms / control)
Number of relays 2(1)
Type 250 VAC – 5 A – 1150 VA
2 inputs / 2 outputs module: Phototransistor inputs
Number 2(1)
Power supply 10 … 30 VDC
Minimum signal width 10 ms
Minimum duration between 2 pulses 18 ms
Type phototransistors
Pulse output module
Number of relays 2
Type 100 VDC – 0.5 A – 10 VA
Max. number of operations ≤ 108
Analogue output module
Number of outputs 2(2)
Type insulated
Range 0 / 4 … 20 mA
Load resistance 600 Ω
Maximum current 30 mA
MODBUS communication module
Link RS485
Type 2 … 3 half duplex wires
Protocol MODBUS RTU
MODBUS® speed 4800 … 38400 bauds
Ethernet communication module
Connection RJ45
Speed 10 base T / 100 base T
Protocol MODBUS TCP or MODBUS RTU over TCP
Temperature module (inputs)
Type PT100
Connection 2, 3 or 4 wires
Dynamic – 20 °C … 150 °C
Accuracy ± 1 digit
Maximum length 300 cm
Operating conditions
Operating temperature – 10 … + 55 °C
Storage temperature – 20 … + 85 °C
Relative humidity 95 %
(1) Max. 3 modules / DIRIS.
(2) Max. 2 modules / DIRIS.

 

Plug-in modules

DIRIS® A60

Pulse outputs
  • 2 configurable pulse outputs (type, weight and duration) on ± kWh, ±kvarh and kVAh.

  Communication MODBUS®
  • RS485 link with MODBUS® protocol (speed up to 38400 bauds).
* With integrated memory module.

Ethernet communication
  • Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
  • Embedded Webserver function(1).

Ethernet communication with RS485 MODBUS gateway
  • Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
  • Connection of 1 to 247 RS485 MODBUS slaves.
  • Embedded Webserver function(1).

Analogue outputs
A maximum of 2 modules may be connected, providing up to 4 analogue outputs.
Per module 2 outputs assignable to:
  • 3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, I sys, Vsys, Usys, Ppred, Q pred, Spred, T°C internal, T°C 1, T°C 2, T°C3 and to 17 VDC power supply.

2 inputs – 2 outputs
  • A maximum of 3 modules may be connected, providing up to 6 inputs and 6 outputs.
  • Per module 2 outputs assignable to:

– monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, SS,ΣPFL/C, THD 3I, THD In, THD 3V, THD 3U, Ppred, Qpred, Spred, internal T°C, T°C 1, T°C2, T°C3 and hour meter,

– remote control,
– timed remote control.
– 2 inputs for pulse metering.

Temperature(2)
Temperature indication:
– internal,
– external sensor PT 100 (T°C 1),
– external sensor PT 100 (T°C 2),
– external sensor PT 100 (T°C 3),.
(1) See “Management software for DIRIS”
(2) See “external sensor PT 100”

 

 Case

DIRIS A60
Type panel mounting
Dimensions W x H x D 96 x 96 x 95 mm
Case degree of protection IP 30
Front degree of protection IP 52
Display type backlit LCD display
Terminal block type fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
Current connection cross-section 0.5 … 6 mm2
Weight 450 g

 

Accessories

Current transformers Split-core current transformers IP65 protection Panel mounting kit
for a 144 x 96 mm cut-out
Current transformers 2 IP65 protection

 

Connection

Recommendation:
– When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
Low voltage balanced network for DIRIS A60
3/4 wires with 1 CT Single-phase Two-phase
Use of 1 CT reduces by 0.5% the accuracy of the phases, the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.  1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Low voltage unbalanced network for DIRIS A60
3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of Use of 2 CTs reduces by 0.5% the accuracy of
the phases, the current of which is worked out the phases, the current of which is worked out
by vector calculation. by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

 

Additional information

Communication via RS485 link Connection of voltage transformer for HV networks AC auxiliary power supply
1. Fuses 0.5 A gG / 0.5 A class CC.

Terminals

DIRIS A60
AUX: auxiliary power supply US
V1, V2, V3 & VN: voltage inputs S1 – S2: current inputs
RS485 MODBUS module
Ethernet module
Ethernet module + RS485 MODBUS gateway
 
RS485 link RS485 gateway resistor
R = 120 Ω: selectable internal resistance for RS485 end of line termination R = 120 Ω: selectable internal resistance for RS485 end of line termination
Pulse output module
Temperature module
2 inputs – 2 outputs module
9 – 10: relay output n°1 17 – 18: synchronisation input Sensor 1 Sensor 2 Sensor 3
11 – 12: relay output n°2 19: red 23: red 27: red
13 – 14: opto input n°1 20: red 24: red 28: red
15 – 16: opto input n°2 21: white 25: white 29: white
22: white 26: white 30: white
Analogue output module
5- 6: analogue output n°1
7 -8: analogue output n°2

 

References

Basic device DIRIS A60
Auxiliary power supply US Reference
110 … 400 VAC / 120 … 350 VDC 4825 0207
Optionals
Plug-in modules (1) Reference
Pulse outputs 4825 0090
RS485 MODBUS® communication 4825 0092
Analogue outputs 4825 0093
2 inputs / 2 outputs 4825 0094
Ethernet communication (Embedded Webserver function) (2) 4825 0203
Ethernet communication + RS485 MODBUS gateway (Embedded Webserver function) (2) 4825 0204
Temperature inputs 4825 0206
(1) Easy integration of additional functions (maximum 3 slots per device).
(2) Dimension of the plug-in module: 2 slots.
Options
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 6 5601 0017
1 pole + neutral
Fuse type gG 10×38 0.5 A 10  6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1
Temperature sensor PT100 – M6 screw type 1 4825 0208
Temperature sensor PT100 – M6 eyelet type 1 4825 0209
Management software for DIRIS